GE Intelligent Platforms > Support >  Drivers - General > DG150
OPM Opto22 Mistic
Type File Name Date Posted Size Description

There are files attached to this record that may require you to login.

 


Description

ProductVersionModule
HMI/SCADA - iFIX All All

Code : OPM
Vendor : GE Intelligent Platforms
Hardware Manufacturer : Opto 22
Notes : Available for use with FIX32 and iFIX only.

General

Platform Latest Version Type
Windows NT, 2000, XP 6.11 RES

Supported
Devices

Device Manufacturer Comment
M4RTU Controllers Opto 22 -
Mistic Controllers Opto 22 -

Additional
Requirements

Software Manufacturer Vendor Part No. Comment
HOSTWORD.EXE Opto 22 Opto 22 - Downloaded from Opto's bulletin board, bbs.opto22.com
OptoControl v3.0 or greater Opto 22 Opto 22 - -
TCP/IP Microsoft Microsoft - Protocol supplied with OS (NT)

Protocol

Type Supported Baud Rates Data Bits Stop Bits Parity Error Checking Hand Shaking Comment
Communication Network Ethernet - - - - - - -

Supported
Data Types

Data Type Comment
ASCII -
Digital -
Float -
Integer -
Structure -

Supported
Memory Types

Device Memory Type Comment
none

Commands

Device Command Description Uses
OPTOSDK API Calls �Mistic Command Set - -

Signal
Conditionings

Signal Type Description Comment Typical Gain Convergance Range
12AL 12 Bit Binary Scaled to EGUs - Alarming on out of range Ignores the most significant 20 bits. Values of more than 12 bits are displayed. - -
12BN 12 Bit Binary Scaled to EGUs- No Alarming on out of range Ignores the most significant 20 bits. - -
15AL 15 Bit Binary Scaled to EGUs - Alarming on out of range Ignores the most significant 17 bits. Values of more than 15 bits are displayed. - -
15BN 15 Bit Binary Scaled to EGUs - No Alarming on out of range Ignores the most significant 17 bits. - -
16AL Scaled to EGU range of database block. Does range checking alarming. Ignores the most significant 2 bytes.    
16BN Unsigned 16-bit digital scaled to EGU range in database block. Cannot determine out of range; therefore does not alarm. Ignores the most significant 2 bytes. - -
LN32 Value scaled to EGU range of block.      
NONE Returns raw value No alarming on out of range. - -

Miscellaneous
Info

Relevant Notes
This driver is designed to communicate to the Opto Mystic and M4RTU controllers through Ethernet, Arcnet, and Serial interfaces.

Intellution tested this driver with the Mistic 200, M4RTU, M4SENET, and M4SARC hardware.

This driver requires the OptoControl API v3.0 or greater, which is available from Opto.

History

Revision History
Reason for 6.00e Release on 1/20/98:
* New driver - designed to talk to Opto Mistic and M4RTU controllers via Ethernet, Arcnet, and serial interfaces.

Reason for 6.00f Release on 6/4/98:
* Corrected problem with variables not updating.

Reason for 6.00g Release on 5/7/99:
* Corrected problem of not being able to edit or display more than 300 poll records in the configurator.

Reason for 6.00h Release on 10/22/00:
* Corrected problem of driver using up all 32 available sessions when a device fails and a reconnect is attempted.

Reason for 6.00i Release on 01/11/00:
* Corrected problem of the driver stopping when a new configuration is loaded.

Additionally, the driver now waits for the delay time to expire before attempting to reconnect to the network.

Reason for 6.00j Release on 4/28/00:
* Implemented signal conditioning for signed Integer and Long data types.

Reason for 6.10 Release on 5/11/01:
* Added support for Optocontrol software v3.1.

Reason for 6.10a Release on 9/17/01:
* The driver was unable to re-establish communication if the connection to both the primary and backup controllers was lost and then regained. Changed the driver so that once either controller resumes normal operation, communication with that controller is re-established.

Reason for 6.11 Release on 7/01/04:
* Added support for OPTO Control Factory Floor Software v4.0.
* Added support Windows 2000 and Windows XP operating systems.


Details
ID: DG150
Category: I/O Drivers
Last Updated: 03/29/10
Date Created: 04/24/00
Status: Published
Attachments: Yes
Language: English


 


Overall Rating: 3.5 (2 responses)
Rate this content record (1=lowest, 5=highest)
5
4
3
2
1
Comment


Note:  If your firewall blocks ZIPS and EXEs, simply right-click and select SAVE TARGET AS and change the extension to something like "XIP".  Once downloaded change the extension back to its original one.

All drivers produced by vendors other than GE ("3rd Party Drivers") are provided by GE "as is" and without warranty of any kind unless the vendor extends a pass-through warranty to the end user.  Support for 3rd Party Drivers is provided by the driver's vendor.