| Type |
File Name |
Date Posted |
Size |
Description |
There are files attached to this record that may require you to login. |
| Product | Version | Module | | HMI/SCADA - iFIX |
All |
All |
Code : SIE
Hardware Manufacturer : Siemens Energy & Automation Inc.
Notes : Available for use with FIX32 and iFIX only.
General
| Platform |
Version |
Type |
| Windows NT4 / 2000 / XP(SP2) / Server 2003 / Vista |
6.40 |
COM |
Supported
Devices
| Device |
Manufacturer |
Comment |
| All Siemens devices with a serial port that supports the 3964r protocol (S5-115, S5-135U, S5-150U, S5-155U) |
Siemens Energy & Automation Inc. |
- |
Additional
Requirements
| Software |
Manufacturer |
Vendor |
Part No. |
Comment |
| none |
Protocol
| Type |
Supported |
Baud Rates |
Data Bits |
Stop Bits |
Parity |
Error Checking |
Hand Shaking |
Comment |
| Direct Link |
Siemens 3964R |
Selectable from 110 to 19200 |
8 |
1 |
Even |
- |
- |
- |
Supported
Data Types
| Data Type |
Comment |
| ASCII |
8-bit character |
| Digital |
On/Off status |
| Float |
32-bit floating point (IEEE) |
| Long |
Unsigned 32-bit integer |
| Signed |
Signed 16-bit integer |
| Unsigned |
Unsigned 16-bit integer |
Supported
Memory Types
| Device |
Memory Type |
Comment |
| none |
Commands
| Device |
Command |
Description |
Uses |
| All |
Read and Write |
- |
- |
Signal
Conditionings
| Signal Type |
Description |
Comment |
Typical Gain |
Convergance Range |
| 11CO |
11 Bit Unsigned Overdrive Range |
Ignores most significant 5 bits. |
- |
- |
| 11CT |
11 Bit Unsigned Transducer Range |
Ignores most significant 5 bits. |
- |
- |
| 11N |
11 Bit Unsigned |
Ignores most significant 5 bits. |
- |
- |
| 11S |
11 Bit Signed |
Ignores most significant 5 bits. |
- |
- |
| 12AL |
12 Bit Binary Scaled to EGUs - Alarming on out of range |
Ignores most significant 4 bits (nibble). |
- |
- |
| 12BN |
12 Bit Binary Scaled to EGUs- No Alarming on out of range |
Ignores most significant 4 bits (nibble). |
- |
- |
| 12S |
12 Bit Signed |
Ignores most significant 4 bits (nibble). |
- |
- |
| 15AL |
15 Bit Binary Scaled to EGUs - Alarming on out of range |
Ignores most significant bit. |
- |
- |
| 15BN |
15 Bit Binary Scaled to EGUs - No Alarming on out of range |
Ignores most significant bit. |
- |
- |
| 3BCD |
3 Digit Binary Coded Decimal |
Scaled to EGUs. Alarming on out of range. Ignores most significant 4 bits (nibble). |
- |
- |
| 4BCD |
4 Digit Binary Coded Decimal |
Scaled to EGUs. Alarming on out of range. |
- |
- |
| 8N |
8 Bit Binary Scaled to EGUs - No Alarming on out of range |
Ignores most significant byte. |
- |
- |
| LIN |
Value scaled to EGUs |
- |
- |
- |
| NONE |
Returns raw value |
- |
- |
- |
| TIME |
Time Base Information |
- |
- |
- |
Miscellaneous
Info
| Relevant Notes |
The SIE driver does not support the Siemens 3964R feature with
"following-on" messages. |
History
| Revision History |
Reason for 6.00b Release on 1/9/97:
* Driver released including all previous SIMs.
Reason for 6.00c Release on 6/25/97:
* Corrected problem of a value of 0.0 in PLC showing in FIX as -0.0 when using Signed data type and Linear signal conditioning.
Reason for 6.00d Release on 1/27/99:
* Driver released including all previous SIMs.
Reason for 6.00e Release on 6/2/00:
* Corrected a problem with poll records with length of 16 were not working. The device always sent NAKs for these poll records.
Reason for 6.01 Release on 03/26/2003:
* Modified documentation to comply with GE standards.
* Tested and validated driver running under Win2000 and WinXP.
Reason for 6.01a Release on 08/17/2005:
* Updated to reflect GE Fanuc branding.
Reason for 6.02 Release on 12/22/2005:
* Driver support for Windows XP and Windows 2003 Server.
Reason for 6.40 Service Pack release on 10/23/2007:
* SIE now validated for use with Microsoft Vista OS.
|
|
|