VersaMax Analog Input Module IC200ALG240, Cable Shield Connections
Description

Description

If possible, analog input channel connections should be grounded at the source device.

Resolution

If that is not possible, the cable shield must be grounded at the I/O module

  1. If the module is installed on a Terminal-style I/O Carrier (IC200CHS001, 002, or 005) or a Compact Terminal-style I/O Carrier (IC200CHS022 or 025), the cable shield can be connected directly to the carrier per the Field Wiring Table. An Auxiliary I/O Terminal Strip (IC200TBM001, 002, or 005) can also be added to the Terminal-style I/O Carriers to aid in grounding shields.
  2. If the module is installed on a Compact Terminal-style I/O Carrier (IC200CHS022, 025), shield connections can be made on an Auxiliary I/O Terminal that is mounted near the I/O carrier. Be sure to ground the Auxiliary I/O Terminal Strip as well if you plan to use it for this purpose.
  3. If the module is installed on a Connector-style I/O Carrier (IC200CHS003), the cable shield can be connected directly to an Interposing Terminal (IC200CHS011, 012, 015). Be sure to ground the Interposing Terminal. It is recommended to use a shielded interposing cable as well between the Interposing Terminal and the Connector Base. A custom shielded cable can be made using the Connector kit (IC200ACC202). In addition, a custom shield braid can be wrapped around standard Interposing Cables (IC200CBL105, 110, 120, 230). If this approach is used be sure to ground the braid.

Field Wiring Table :

Refer to manual GFK-1504k, page 10-11, for field wiring information.


ProductVersionModule
VersaMax All All


Details
ID: KB9427
Legacy ID: i025522
Category: Articles
Last Updated: 07/16/12
Date Created: 08/09/06
Status: Published
Attachments: No
Language: English
User Group: All


 


Overall Rating: 3 (1 response)
Rate this content record (1=lowest, 5=highest)
5
4
3
2
1
Comment